Nordic System Disturbance
- country Sweden
- region Stockholm
- categories No content
- impacts Balancing authority events
- start 26 April 2023 at 06:04:00 Europe/Stockholm
- end 26 April 2023 at 06:04:00 Europe/Stockholm
- duration 12 minutes
- primary cause Human error
- secondary causes No content
- load lost No content
- number of customers affected No content
- end of disturbance criteria No content
why this is interesting
No content here.
description
- On April 26th the 400 kV voltage in Sweden dropped to 250 kV (0.62pu) for 7 seconds following a "manual error during maintenance of a substation".
- System was N-1 secure and reserves available to cover a 1.4GW loss
- Generation was 17GW. Load was 14.6 GW
- The event started when someone tried to open a 220 kV disconnect remotely, but that didn't work because the interlock logic indicated the disconnect was in the intermediate position
- The interlock logic said that it was in the intermediate position because the control cabinet had been demolished and no longer existed
- So, the switching operators bypassed the interlocking locally and then opened the wrong disconnect
The current through the disconnect exceeded its rating, so it flashed over as a 2-phase fault and then evolved to a 3PH fault - Duplicate 220 kV busbar protection existed and both tripped, but one bay failed to open due to two separate failures of the protection design
- The phase voltage in the area dropped to approx 0.6pu
- Nearby Forsmark 1 & 2 nuclear gens both tripped from 2.13GW about 1 second later
- The fault was finally isolated after 7 seconds by transformer undervoltage protection
- After fault isolation, the voltage recovered and hit 1.17pu for several seconds before generators responded and down-regulated voltage again
- A total of 25 cap and reactor banks tripped due to the low and high voltage conditions
- The frequency fell to 49.3 Hz and recovered to 49.9 Hz about 12 minutes later